How to thaw a frozen condensate pipe

Quick answer

Find the plastic pipe that runs from the boiler to an outside drain. Warm the exposed outside part with a hot water bottle or warm water from a watering can, never boiling water, then reset the boiler.

Condensing boilers produce waste water that drains through a plastic pipe, usually to an outside drain. When it's below zero, water in the exposed part of the pipe can freeze and block it. The boiler then shuts down and usually shows a fault code. Common ones are EA 227 or EA 229 on Worcester Bosch, L2 or F2 on Ideal, F.28 on Vaillant and Glow-worm, and E133 on Baxi. Baxi says this also applies to its E23, E53, E119 and E128 codes.

  1. Turn the boiler off, at its controls and then at the fused spur on the wall.
  2. Find the frozen section. It's usually the most exposed bit outside, often at a bend or the open end near the drain.
  3. Warm it. Use a hot water bottle, a microwaveable heat pack, or warm water from a watering can poured along the pipe. Baxi warns against using boiling water straight from the kettle, as it can damage the pipe.
  4. Turn the power back on and reset the boiler. If it doesn't restart, warm the pipe again and repeat.

Only deal with the plastic pipe outside. Don't open the boiler or take apart the condensate trap.

Stop it happening again

Weatherproof insulation on the outside run helps. A heating engineer can also reroute or upsize the pipe so it drains faster, which is often the permanent fix.